The National Institute of Standards and Technology (NIST) has released its final report on its study of the June 18, 2007, fire at the Sofa Super Store in Charleston, S.C., that trapped and killed nine firefighters, the highest number of firefighter deaths in a single event since 9/11. The final report is strengthened by clarifications(澄清,说明) and supplemental(补充的) text based on comments provided by organizations and individuals in response to the draft report of the study, released for public comment on Oct. 28, 2010. The revisions did not alter the study team's main finding: the major factors contributing to the rapid spread of the fire at the Sofa Super Store were large open spaces with furniture providing high-fuel loads, the inward rush of air following the breaking of windows, and a lack of sprinklers(洒水装置) .

#

Based on its findings, the study team made 11 recommendations for enhancing building, occupant and firefighter safety nationwide. In particular, the team urged state and local communities to adopt and strictly1 adhere to current national model building and fire safety codes. These codes are used as models for building and fire regulations promulgated2(发布,公布) and enforced by U.S. state and local jurisdictions3. Those jurisdictions have the option of incorporating some or all of the code's provisions but often adopt most provisions. #

If today's model codes had been in place and rigorously followed in Charleston in 2007, the study authors said, the conditions that led to the rapid fire spread in the Sofa Super Store probably would have been prevented.

#

Specifically, the NIST report calls for national model building and fire codes to require sprinklers for all new commercial retail5 furniture stores regardless of size, and for existing retail furniture stores with any single display area of greater than 190 square meters (2,000 square feet). Other recommendations include adopting model codes that cover high fuel load situations (such as a furniture store), ensuring proper fire inspections6 and building plan examinations, and encouraging research for a better understanding of fire situations such as venting7(排放) of smoke from burning buildings and the spread of fire on furniture.

#

Two of the recommendations in the draft report were slightly modified to increase their effectiveness. The recommendation "that all state and local jurisdictions(行政辖区) ensure that fire inspectors8 and building plan examiners are professionally qualified9 to a national standard" was improved by listing three nationally accepted certification examinations as examples of "how professional qualification may be demonstrated." Another recommendation has been enhanced by urging state and local jurisdictions to "provide education to firefighters on the science of fire behavior in vented#p#分页标题#e#4 and non-vented structures and how the addition of air can impact the burning characteristics of the fuel."

#

NIST is working with various public and private groups toward implementing10 changes to practices, standards, and building and fire codes based on the findings from this study. #